Linear and rotary 90º
Application: double- and single-acting pneumatic actuators
General Data
Type: | PS 2 |
Material: | Glass fibre reinforced polycarbonate |
Protection class: | IP65 |
Supply Air: | 1,4-7 bar instrument air |
oil, hiking and dust (<30μm) | |
Max. air consumption: | 5,5 m³/h at 6,5 bar control air |
Stationary air consumption: | <3,6x10-2m³/h |
Position indication: | Display |
Input Signal: | 4-20mA; 2 wire |
Option: 3 or 4 wire | |
Impedance: | 320 Ω |
Mounting: | Stainless steel AISI 304 |
Positioner Connection: | NAMUR |
Ambient Temperature: | -30ºC to +80ºC |
Options: | Extension modules for position feedback |
Alarms / error reports | |
Inductive Sensors | |
Versions for EEx areas with manometer block and metal housing |
Item No. | Actuator Type | Description |
---|---|---|
40504000 | Single-action | PS2 EV excl. mounting |
40505400 | Double acting | PS2 DV excl. mounting |
97680061 | Single acting | PS2 EV incl. mounting of S actuators |
Item No. | Actuator Type | Dimensions |
---|---|---|
40504050 | Linear | PS2 for 2-35 mm migration |
40502001 | 90º rotating | PS2 for 30 x 80 mm hole |
40502002 | 90º rotating | PS2 for 30 x 130 mm hole |
Item no. | Type | Description | Other |
---|---|---|---|
40508094 | 6 DR 4004-8A | Alarm Module | - |
40505050 | 6 DR 4004-8J | Position Module | 4-20mA signal |
40508089 | 6 DR 4004-8J | HART module | - |