Direct-acting or reverse-acting T105 T106
Application: Temperature controlling of heating, cooling systems and industrial processes
General Data
Type: | T105 / T106 |
Material: | Stainless steel AISI 316 (sensor tube / wetted parts) |
Other materials: | Chrome-plated brass and stainless steel |
Connection: | 1/2" or 1" BSP nipple |
Clamp acc. to ISO 2852 ø38, ø51 and ø76,1 mm | |
Proportional Band: | 4% (+/- 2% of temperature range) |
Supply air: | 1,5 bar instrument air |
oil, water, dust-free (<30μm) | |
Outlet control: | 0,2 to 1 bar (3-15PSI) |
Stationary air: | 2 Nl / min |
Air connection: | 1/8" BSP female |
Sensor length: | 275 mm, ø12 mm |
Temperature Range: | 0°C to +100ºC |
-10ºC to +90ºC | |
Options: | Proportional Band: 2% (+/- 1% of temperature range) |
Item No. | Temperature Range (Cº) | Connection |
---|---|---|
97600031 | 0 - 100 | 1/2" RG |
97600032 | 0 - 100 | 1" RG |
97600040 | 0 - 100 | DN 38mm / Clamp Ø 50,5mm |
97600041 | 0 - 100 | DN 51mm / Clamp Ø 64mm |
Item No. | Temperature Range (Cº) | Connection |
---|---|---|
97600012 | 0 - 100 | 1/2" RG |
97600038 | 0 - 100 | 1" RG |
97600011 | 0 - 100 | DN 38mm / Clamp Ø 50,5mm |
97600045 | 0 - 100 | DN 51mm / Clamp Ø 64mm |